Bailey has developed an insulation package for most Aerial Work Platform brands consisting of a fiberglass boom assembly and a wireless or fiberoptic interface between the platform and ground controls. Our team of Professional Engineers have designed over 25 systems on boom lifts and scissor lifts.
Insulated regulations are identified in ANSI A92.2 with the Voltage Rating Table shown below. Call us for application information.
Unit Rating | Required 60 Hertz Rated Voltage Test | Required 60 Hertz Double-Rated Voltage Test | Either of These Withstand Tests | |||
---|---|---|---|---|---|---|
Rated Line Voltage (nns kV) | One Minute Test Voltage (nns kV) | Maximum Allowable Boom Current (rms microaperes) | One Minute Test Voltage (nus kV) | Maximum Allowable Boom Current (nns microamperes) | 60 Hertz Two (2) Second Withstand Voltage Test (nns kV) | Switching Surge Withstand Voltage Test (crest kV) |
46 & below 69 138 230 345 500 765 |
27 40 80 133 200 288 442 |
27 40 80 133 200 288 442 |
54 80 160 265 400 578 885 |
54 80 160 265 400 578 885 |
80 120 240 400 600 720 1105 |
114 170 340 565 850 1020 1560 |
Available on Boom Lifts in sizes 40-120 feet.
Call for information on sizes for the Scissor Lifts